220 volt wire size calculator

Estimate wire area for a 220 V two-wire load and compare maximum one-way runs for common metric conductor areas at your current.

Calculator

Conductor area
0.000001
Conductor area (mm²)
0.50909091
Equivalent bare round-wire diameter
0.000805
One-way run length
10
Load current
10
Allowed voltage drop
6.6
Voltage at the load at this limit
213.4
Source power for the resistive load
2,200
Operating resistivity (nano-ohm metres)
16.80000000
Temperature coefficient (1/K)
0.00390000
AWG meeting the area criterion
AWG 20; voltage-drop criterion only
220 V maximum runs at your current and drop limit
Conductor area (mm²)Maximum one-way length (m)
1.5000000029.46428571
2.5000000049.10714286
4.0000000078.57142857
6.00000000117.85714286
10.00000000196.42857143
16.00000000314.28571429
25.00000000491.07142857
35.00000000687.50000000
50.00000000982.14285714
Scientific notation
QuantityValue in stated units
Conductor area (m2)5.09090909e-7

Advertisement

How this calculator works

This page fixes source voltage at 220 V and models two conductors supplying a DC or unity-power-factor single-phase load. The metric-size table converts the chosen percentage drop into maximum lengths for areas from 1.5 to 50 mm². Copper and aluminium use representative 20 C resistivity and alpha = 0.0039/K; custom material properties are also available. Bare-wire diameter is calculated from area, so it excludes insulation. A nominal 220 V label does not describe every local supply. Use the actual supply voltage in the general calculator when it differs, and check thermal capacity and local wiring requirements independently.

Formula

DeltaV = k rho(T) L I/A; A = k rho(T) L I/DeltaV; L = DeltaV A/(k rho(T) I); I = DeltaV A/(k rho(T) L). For two wires k = 2; for balanced three-phase k = sqrt(3). rho(T) = rho20[1 + alpha(T - 20 C)].

Worked example

At 220 V, a 3% allowance is 6.6 V. A 20 A load 30 m away requires 3.05455 mm² of copper at 20 C by voltage drop. A 2.5 mm² copper conductor at 10 A reaches the same 3% limit after 49.1071 m one-way.

Advertisement

Frequently asked questions

Can I use this for a 230 V or 240 V supply?

Use the general wire size calculator with that voltage. This focused page keeps 220 V fixed so its metric-size table has a consistent reference.

Are the table lengths permitted installation lengths?

They satisfy only the entered resistance-based drop limit. Thermal limits, protection, installation method and equipment terminals can impose tighter constraints.

Does this cover a motor with low power factor?

The two-wire model assumes resistive voltage drop and omits cable reactance. A full AC voltage-drop calculation is needed when phase angle matters.