100 amp wire size calculator

Estimate conductor area for a 100 A load from voltage drop, compare common run lengths, or check the distance supported by an existing area.

Calculator

Conductor area
0.000009
Conductor area (mm²)
9.33333333
Equivalent bare round-wire diameter
0.003447
One-way run length
10
Load current
100
Allowed voltage drop
3.6
Voltage at the load at this limit
116.4
Source power for the resistive load
12,000
Operating resistivity (nano-ohm metres)
16.80000000
Temperature coefficient (1/K)
0.00390000
AWG meeting the area criterion
AWG 7; voltage-drop criterion only
100 A run-length comparison at your voltage and drop limit
One-way distance (m)Required area (mm²)
1.000000000.93333333
5.000000004.66666667
10.000000009.33333333
20.0000000018.66666667
30.0000000028.00000000
50.0000000046.66666667
100.0000000093.33333333

Advertisement

How this calculator works

The area and distance modes hold load current at 100 A. A run-length table shows how the area requirement changes from 1 to 100 metres at your source voltage. The current mode checks a known conductor against the same drop limit. Results use one conductor area and one-way distance; the return path is included. Copper and aluminium use rounded textbook resistivity at 20 C and alpha = 0.0039/K. These estimates do not establish a conductor ampacity or a compliant 100 A service size. Cable reactance, terminals, insulation, installation method and protective devices need separate checks.

Formula

DeltaV = k rho(T) L I/A; A = k rho(T) L I/DeltaV; L = DeltaV A/(k rho(T) I); I = DeltaV A/(k rho(T) L). For two wires k = 2; for balanced three-phase k = sqrt(3). rho(T) = rho20[1 + alpha(T - 20 C)].

Worked example

For 100 A at 120 V, a 3% drop permits 3.6 V. Copper at 20 C over 10 m one-way requires 9.3333 mm² by resistance alone. At 240 V, a 25 mm² copper conductor reaches the 3% limit at 53.5714 m one-way.

Advertisement

Frequently asked questions

Does this tell me the code size for a 100 A panel?

No. A voltage-drop calculation cannot determine service or feeder ampacity. Use the applicable installation rules and equipment ratings for that decision.

Why does changing 120 V to 240 V change area?

At the same 100 A and percentage limit, twice the voltage allows twice the voltage drop and therefore half the resistance-based conductor area.

What does the run table hold constant?

It holds current at 100 A and retains your voltage, material, temperature, circuit geometry and percentage drop. Only one-way distance changes.