Voltage drop calculator

Enter one-way conductor length and the cross-sectional area of one conductor. This estimate includes conductor resistance and excludes reactance.

Calculator

Assumes identical length, area and material, sharing current equally.

Voltage drop
3.36
Estimated load voltage
116.64
Voltage drop fraction
2.8000%
Required conductor area
0.000002
Total conductor heat loss
33.6

Advertisement

How this calculator works

Wire resistance is resistivity times length divided by conductor area. A two-wire circuit includes an outgoing and return path, giving a factor of two. The balanced three-phase line-to-line approximation uses sqrt(3). AC voltage-drop estimation projects the resistive drop using displacement power factor and neglects reactance, while conductor heating still uses I²R. AWG modes derive the bare conductor area from gauge; parallel-conductor mode assumes identical wires sharing current equally. Use the actual hot-conductor resistivity. This calculation does not determine ampacity, protective devices or compliance with an electrical code.

Formula

DC: deltaV = 2 rho L I/(A p). AC resistance-only approximation: deltaV = k rho L I PF/(A p), k = 2 single phase or sqrt(3) three phase, p = identical parallel conductors per leg. Pwire = nlegs I² rho L/(A p). AWG diameter d = 0.000127 × 92^((36-gauge)/39) m; A = pi d²/4.

Worked example

A 20 m one-way DC run with rho = 1e-8 ohm m, area 2e-6 m² and current 10 A drops 2 V. A 120 V source therefore gives an estimated 118 V at the load.

Advertisement

Frequently asked questions

Do I enter the round-trip length?

No. Enter the one-way run. The two-wire return is already included.

Can this size a cable for installation?

It estimates area for voltage drop only. Thermal limits, installation conditions and electrical-code requirements need separate checks.

When is the AC estimate inadequate?

Long runs, low power factor or cables with appreciable reactance need a full phasor impedance calculation.