Transformer sizing calculator

Enter RMS load voltage and line current. Three-phase voltage is line-to-line. The spare allowance adds a chosen percentage of the present load.

Calculator

Present load (VA)
12,000.00000000
Present load (kVA)
12.00000000
Capacity with allowance (VA)
15,000.00000000
Capacity with allowance (kVA)
15.00000000
Example next catalogue rating
15 kVA; confirm availability and application rating

Advertisement

How this calculator works

Transformer thermal loading is described by apparent power in volt-amperes, rather than real watts alone. Single-phase apparent power is voltage times current, while a balanced three-phase load uses the square root of three multiplier with line quantities. The spare percentage is added to present load, so 25% spare means 1.25 times current VA, not 75% utilisation. Example catalogue sizes are illustrative; starting currents, harmonics, cooling and manufacturer derating need separate assessment.

Formula

Ssingle = VI; Sthree = sqrt(3) Vline Iline; Srequired = Sload(1+allowance); kVA = VA/1000.

Worked example

A single-phase 120 V, 100 A load is 12000 VA or 12 kVA. Adding 25% load allowance gives 15000 VA or 15 kVA.

Advertisement

Frequently asked questions

Is the spare percentage a utilisation limit?

No. It adds a fraction of the present load. A 25% addition corresponds to 80% use of the resulting capacity.

Can I size a motor supply from running current alone?

Starting current and allowable voltage dip can require a larger transformer; check the manufacturer's application data.

Is the suggested size a complete equipment recommendation?

No. It is the next example catalogue rating and does not check voltage ratio, impedance, protection or installation conditions.