Heat loss calculator

Estimate steady sensible heating demand from exposed area, effective U-value and air changes. Choose room geometry or a measured envelope area.

Calculator

Total heat loss
1.526
Envelope heat loss
1.275
Air-exchange heat loss
0.251
Effective U-value (W/m2 K)
1.000
Indoor temperature
20
Exposed area
42.5
Heat-loss components
ComponentPower (W)
Envelope1,275.000
Air exchange251.250

Advertisement

How this calculator works

Envelope heat loss follows U x area x temperature difference. Known-area mode uses an area-weighted U-value that accounts for the complete surface. Room mode subtracts entered window and door areas from the exposed walls and adds their separate U-value losses. The main U-value applies to the remaining opaque envelope. Room mode treats the exposed walls in order: length, adjacent width, second length, second width. Floor and ceiling use the same effective U-value as a simplifying assumption. Air exchange adds sensible loss using an approximate air volumetric heat capacity of 1206 J/(m3 K), using 1.2 kg/m3 air density and 1005 J/(kg K) specific heat. Moisture, solar gains, heat recovery and warm-up are excluded.

Formula

Q = [sum of each surface U x area + 1206 x volume x ACH / 3600] x (Ti - To); Inverse opaque U subtracts window, door and ventilation conductance before dividing by opaque area.

Worked example

A 10 m2 surface with U = 2 W/(m2 K) across a 30 K difference loses 600 W without air exchange. A 900 W measured loss across the same surface and temperatures implies U = 3 W/(m2 K).

Advertisement

Frequently asked questions

How do I include windows and doors?

Room mode uses repeated opening dimensions with separate window and door U-values. Known-area mode instead expects a combined area-weighted U-value.

Is this a whole-house equipment design?

It is a steady estimate. A room-by-room design must account for different assemblies, design weather, infiltration and distribution losses.

Can I solve for indoor temperature?

Yes. That mode finds the steady balance temperature from useful heating power under the entered envelope and ventilation assumptions.