Air changes per hour calculator

Relate measured airflow to room volume, or solve for the airflow needed to reach a chosen air change rate.

Calculator

Air changes per hour (1/h)
6.000
Airflow
360
Floor area
20
Ceiling height
3
Room volume
60
Airflow (CFM)
211.888

Advertisement

How this calculator works

Multiply floor area by ceiling height to obtain room volume. Divide hourly air delivery by that volume. This is a nominal mixing calculation: supply air, outdoor air and filtered clean air are different quantities. Use the airflow relevant to your purpose and do not count the same air twice.

Formula

ACH = 3600 x Q / (A x H), where Q is m3/s, A is m2 and H is m. Rearrange the same equation for airflow, area or height.

Worked example

A 20 m2 room with a 3 m ceiling contains 60 m3. An airflow of 360 m3/h provides 6 air changes per hour; 3 changes require 180 m3/h.

Advertisement

Frequently asked questions

Does one air change replace every molecule?

No. Mixing leaves some of the original air in the room after one nominal air change.

Can I use recirculated airflow?

Use it only for the question you are assessing. Unfiltered recirculation is not equivalent to fresh outdoor air or filtered clean air.

What rate should I target?

The appropriate rate depends on occupancy, activity and applicable ventilation guidance. The calculator converts a chosen rate; it does not set a universal target.