Coefficient of performance calculator

Compare the heat moved by a refrigerator or heat pump with its work input. Both heating and cooling COP are reported.

Calculator

Refrigerator COP
5.00000000
Heat-pump COP
6.00000000

Advertisement

How this calculator works

COP measures heat moved per unit work, so it can exceed one without creating energy. A cyclic device satisfies Qh = Qc + W, giving heating COP exactly one greater than cooling COP when both describe the same boundary and operating point. Carnot COP is the reversible upper limit for the specified reservoirs, not a rating for real equipment. Energies may be replaced by consistent steady rates when forming a ratio.

Formula

COPr = Qc/W; COPhp = Qh/W = COPr + 1; Carnot COPr = Tc/(Th - Tc), COPhp = Th/(Th - Tc).

Worked example

A device removing 1000 J while using 200 J of work delivers 1200 J, with cooling COP 5 and heating COP 6. The reversible limits between 250 K and 300 K are also 5 and 6.

Advertisement

Frequently asked questions

Can COP be greater than 100%?

COP is a ratio of moved heat to work, not conversion efficiency; values above one are normal.

What happens when reservoir temperatures match?

The ideal expression diverges. A finite practical device still needs a temperature difference and other constraints.

Can I compare heating and cooling labels directly?

Only when they use the same operating conditions and account for the same auxiliary inputs.