Mixed air temperature calculator

Estimate the temperature of two mixed air streams when their specific heats are equal and moisture effects can be neglected.

Calculator

Mixed air temperature
295

Advertisement

How this calculator works

An adiabatic mixing balance with equal specific heats makes temperature a mass-flow-weighted average. The fraction mode therefore uses stream 1 mass fraction. The volume-flow approximation is valid only for equal densities or flow rates converted to one common reference state. If inlet densities or humidity differ materially, use the full mixed-air tool, which balances dry-air mass, water vapour and enthalpy.

Formula

Tmix = f T1 + (1 - f)T2; f = m1/(m1 + m2). At a common reference density, f = Vdot1/(Vdot1 + Vdot2).

Worked example

Mixing one part of 280 K air with three parts of 300 K air gives 295 K. Equal mass flows at 290 K and 310 K give 300 K.

Advertisement

Frequently asked questions

Does the fraction have to total 100%?

Only stream 1 is entered; stream 2 automatically makes up the remainder.

Can the result be outside both inlet temperatures?

Not for passive adiabatic mixing under these assumptions.

Should I use actual inlet volume flows at different temperatures?

For better accuracy, use the full mixed-air calculator to account for different inlet densities and moisture.

Sources